12F614 - 3Ø Solid Dielectric Recloser, Bi-Directional

Revision 3
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Min. 50 ft. pole required for installation on joint pole.
  2. New reclosers will include two control transformers and a transfer switch inside the control panel. Refer to Compatible Unit BA10B.
  3. Two wedge connectors per switch are required to install line tap switches. Appropriate wedge connector size is listed in Compatible Unit D0520.
  4. Important — disconnect and bypass switches must be accessible to a service truck. Refer to T&D Guideline 4-2-1.1 for equipment accessibility criteria.
  5. Unless specified by Planning and Protection, install the DA antenna, conduit, and coax. If the radio box is not present, coil the coax near the control panel. Seal the end of the coax cable with aqua seal and "88" tape. Refer to Compatible Unit J0401 for more information.
  6. Telecom & System Protection will determine and assign the type of antenna to install. See Compatible Unit J0401 & J0402 for additional information.

 

 

Note: Drill holes as required to obtain switch spacing shown above.

Material List

Compatible Unit Description Quantity
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 86'
DB0210 Recloser, 3Ø 14kV 630A STS Solid Dielectric Bi-Directional 1
D0502 Switch, 600A 15kV Disconnect Xarm Mount 6
D0520 Switch, 600A 15kV Line Tap 3
F0230 Riser, 3" PVC - Control Cable 1
I0103 Insulator, Spool w/ Rack #2 1
I0322 Insulator, 15kV Polymer Suspension 4
I0329 Insulator, 15kV Polymer Suspension 1
J04016 DA Antenna Installation 1
N0110 Plate, Cu Ground 288 in2 1
R0302 Capacitor Bank and Control & Protective Equipment Racks 1
R1115 Split Bolt Assembly, Pole Top 1
R1801 Bracket, Standoff with 12" T-Slot 1
T030* Clamp, Straight Line 6
T0714 Terminal, Comp Captive Bolt 4/0 kcmil AAC/CU 18
T0924 Bar, Extension Terminal Single Tap 15
T0925 Bar, Extension Terminal Double Tap 3
W0201 Holder, Plastic 15kV OH Switch Number 21" x 4" 2
X0301D Crossarm, 10' Double Tangent Fiberglass 1
Z0102 Clamp, Hotline #2 Al 6-336.4 kcmil 8
Z069+ Connector, Mini-Wedge 1
Z063* Connector, Wedge 12
Z064* Connector, Wedge 6
Z0701 Connector, C-Crimp #4 to #4 2