12U314A DE 3Ø UG Terminal Pole (1100kcm Al)

Revision 6
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Note:

  • Individually connect each 1100 kcmil cable's concentric neutral (24 - #14 Cu, equivalent to 1/0 Cu) to a 4/0 Cu neutral bus. Extend the 4/0 Cu neutral bus down to the system neutral and connect it using the appropriate size wedge connector, i.e., Compatible Unit Z0637 4/0 Cu - 3/0 AAC and Compatible Unit Z0642 4/0 Cu - 336.4 AAC. See Compatible Unit page Z0631 - Z0659 for wedge connectors for other neutral conductor sizes.
 
Compatible Unit Description Qty
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 30
C0707 Wire, 4/0 Cu 19-Str SD 15
D0502 Switch, 600A 15kV Disconnect Xarm Mount 3
F0216 Riser, 6" PVC w/ 90° Fiberglass Bend - 3Ø 750 or 1000 kcmil Primary 1
I0103 Insulator, 600V #2 Single Point Secondary Rack 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 2
I0327 Insulator, 15kV Polymer Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 3
N0110 Ground Plate Installation on Wood Pole 1
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 3
T010+ Clamp, Preformed 1
T030* Clamp, Straight Line 3
T0700 Compression Terminal, 336.4 kcmil AAC 2-Hole (Straight) 3
T0704 Compression Terminal, 336.4 kcmil AAC 2-Hole (90°) 6
T0954 SS Bolt, 1/2” x 2” 12
T1006 Cable Term, 1000 kcmil Al Jacketed 3
X0212 Crossarm, 10' Deadend 4-Pos. Hvy. Duty 1
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z0102 Clamp, Hotline Al (#2) #6-336.4 kcmil 3
Z065+ Connector, Wedge 1
Z069+ Connector, Wedge 1
Z0707 Connector, C-Crimp Cu 3/0-4/0 to #6-#2 3
Z0708 Connector, C-Crimp Cu 3/0-4/0 to 1/0-2/0 3
Z0709 Connector, C-Crimp Cu 3/0-4/0 to 3/0-4/0 1