12F613 - 3Ø Distribution Automation Recloser/Sectionalizer
Revision 6
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
Notes:
- Min. 50 ft. pole required for installation on joint pole.
- Important — if there is only one control transformer, connect the transformer to the source side! New reclosers will include two control transformers and a transfer switch inside the control panel. Contact Planning and Protection to determine if you need to order a separate transformer.
Refer to Compatible Unit BA10B. Control transformer is internally fused and does not require a cutout. - Two wedge connectors per switch are required to install line tap switches. Appropriate wedge connector size is listed in Compatible Unit D0520.
- Important — disconnect and bypass switches must be accessible to a service truck.
- Antenna may be specified separately if needed for communications. Refer to Compatible Unit J0401 and J0402 for more information.
Note: Drill holes as required to obtain switch spacing shown above.
Compatible Unit | Description | Quantity |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 86' |
DB0210 | Recloser, 3Ø 14kV 630A STS Solid Dielectric Bi-Directional | 1 |
D0520 | Switch, 600A 15kV Line Tap | 3 |
F0230 | Riser, 3" PVC - Control Cable | 1 |
I0103 | Insulator, Spool w/ Rack #2 | 1 |
I0322 | Insulator, 15kV Polymer Suspension | 4 |
I0329 | Insulator, 15kV Polymer Suspension | 1 |
N0110 | Plate, Cu Ground 288 in2 | 1 |
R0302 | Capacitor Bank and Control & Protective Equipment Racks | 1 |
R1115 | Split Bolt Assembly, Pole Top | 1 |
R1801 | Bracket, Standoff with 12" T-Slot | 1 |
T030* | Clamp, Straight Line | 6 |
T0714 | Terminal, Comp Captive Bolt 4/0 kcmil AAC/CU | 18 |
T0924 | Bar, Extension Terminal Single Tap | 12 |
T0925 | Bar, Extension Terminal Double Tap | 3 |
T0953 | Stainless Steel Bolt Assembly | 6 |
W0201 | Holder, Plastic 15kV OH Switch Number 21" x 4" | 2 |
X0301D | Crossarm, 10' Double Tangent Fiberglass | 1 |
Z0102 | Clamp, Hotline #2 Al 6-336.4 kcmil | 7 |
Z060+ | Connector, H-Type Al Compression | 1 |
Z063* | Connector, Wedge | 12 |
Z064* | Connector, Wedge | 6 |
Z0701 | Connector, C-Crimp #4 to #4 | 2 |