12F608 Obsolete - 15kV Sectionalizer Installation (Vacuum Interrupter Type)

Revision 11
Dec 20, 2016

Notes:

  1. Engineer must specify Compatible Unit for desired sectionalizer:
    DB0404 - 400 amp (Obsolete)
    DB0405 - 600 amp Obsolete)
  2. Sectionalizer is to be mounted on load side of pole.
  3. Disconnect switches are to be mounted with the hinges away from the sectionalizer.
  4. Cutout to be fused with a 1 amp T-link (MID 346016).
  5. Minimum pole height: 45’

 

 

Material List

Compatible Unit Description Quantity
C0113 Wire, 336.4 kcmil AAC 19-str 70
DB040- Sectionalizer, 3Ø 15kV (Josyln VBM) 1
D0502 Switch, 600A 15kV Disconnect Xarm Mount 6
E0202 Cutout, LB 7.8/13.5kV 1
I0103 Insulator, Spool w/ Rack #2 1
I0322 Insulator, 15kV Polymer Suspension 4
I0329 Insulator, 15 kV Polymer Suspension 1
N0110 Plate, Cu Ground 288 in2 1
R0102 Bracket, Cutout Crossarm Mount 1
R1115 Split Bolt Assembly, Pole Top 1
T0303 Clamp, Straight Line 3/0-477 AAC & ACSR 6
T0704 Terminal, Comp 90° 336.4 kcmil AAC 9
T0711 Terminal, Comp Captive Bolt 336.4 kcmil AAC 15
T0924 Bar, Extension Terminal Single Tap 6
T0925 Bar, Extension Terminal Double Tap 6
T0953 Stainless Steel Bolt Assembly 18
X0414 Crossarm, Wood 4-Pin 10' 1
Z010* Clamp, Hotline 1
Z067+ Connector, Mini-Wedge 1
Z063+ Connector, H-Wedge 6
Z0701 Connector, C-Crimp Cu #4 to #4 2