12F312 - 3Ø Double Deadend Underbuild

Revision 7
Jan 10, 2024

 

Notes:

  1. Preferred spacing between crossarm and neutral is 8’-0”. Minimum spacing is 7'-0".
  2. Two primary down guys are required for line angles equal to or greater than 30°. Use one primary guy for line angles less than 30°.
  3. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  4. Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
  5. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For framing conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F376.
  6. Maximum Line Angle: 60 degrees

Material List

Compatible Unit Description Quantity
A0102 Anchor, 12" Single Helix 1
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 30
G0111 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) 1
G0113 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 2
I0103 Insulator, #2 Single Point Secondary Rack 2
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 3
I0321 Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) 6
R1115 Split-Bolt, Pole Top 1
T010+ Deadend, Preform 2
T030* Clamp, Straight Line Deadend 6
X0212 Crossarm, 10' Deadend 4-Pos. Hvy. Duty 1
Z063* Connector, Wedge 6