G0111-2 - 3/8" & 1/2" Down Guy, Fiberglass Strain Insulator, 20' Lead on 45' Pole, 1 Bolt/2 Lag Mounting Hardware
Revision 2
Apr 27, 2023
- This is an alternate to Compatible Unit G0113 and G0114 for situations where a second machine bolt cannot be installed because of short guy leads or pole splitting.
- Do not use this construction in locations where the angle of the guy wire with respect to the pole exceeds 45°.
- Bolt spacing on multiple guys should not be closer than 6”. Use split bolts (R1115) if two guys are placed within any 2’ pole section in the same vertical plane.
Compatible Unit | Guy Size | Item | Description | Qty | MID |
---|---|---|---|---|---|
G0111 | 3/8" | A | Bolt, Machine 3/4” x 14” | 1 | 124595 |
B | Screw, Lag 1/2” x 4” | 2 | 1003315 | ||
C | Wire, Guy EHS 3/8” Galv Stl 7-Str | 56' | 858623 | ||
D | Deadend, Guy Preformed 3/8” | 3 | 880452 | ||
E | Hook, Combination Guy | 1 | 884579 | ||
F | Marker, Guy Yellow Plastic 8’ | 1 | 900052 | ||
G | Washer, Cast Sq 4” Curved 15/16” Hole | 1 | 910035 | ||
H | Deadend, Guy Automatic 3/8” | 1 | 923418 | ||
I | Insulator, Strain FG 78” | 1 | 5005703 | ||
J | Washer, Galv Double Coil Spring Lock 3/4” | 1 | 1001445 | ||
K | Link Clevis, Double Eye (Figure 8) 30,000 UTS | 1 | 927155 | ||
L | Clevis, Y-Clevis 30,000 lb UTS | 1 | 926222 | ||
G0112 | 1/2" | A | Bolt, Machine 3/4” x 14” | 1 | 124595 |
B | Screw, Lag 1/2” x 4” | 2 | 1003315 | ||
C | Wire, Guy EHS 1/2” Galv Stl 7-Str | 56' | 858748 | ||
D | Deadend, Guy Preformed 1/2” | 3 | 880460 | ||
E | Hook, Combination Guy | 1 | 884579 | ||
F | Marker, Guy Yellow Plastic 8’ | 1 | 900052 | ||
G | Washer, Cast Sq 4” Curved 15/16” Hole | 1 | 910035 | ||
H | Deadend, Guy Automatic 1/2” | 1 | 923426 | ||
I | Insulator, Strain FG 78” | 1 | 939209 | ||
J | Washer, Galv Double Coil Spring Lock 3/4” | 1 | 1001445 | ||
K | Link Clevis, Double Eye (Figure 8) 30,000 UTS | 1 | 927155 | ||
L | Clevis, Y-Clevis 30,000 lb UTS | 1 | 926222 |