12F316 - 3Ø Tangent w/ 3Ø Buck

Revision 9
Aug 31, 2020

Notes:

  1. Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
  2. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  3. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F365.

 

Material List

Compatible Unit Description Quantity
A0102 Anchor, 12" Single Helix 1
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 36
G0111 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) 1
G0115 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment 2
I0103 Insulator, #2 Single Point Secondary Rack 2
I0390 Insulator, Sgl Pole Top Pin w/ Polymer Vise-Top Insulator 1
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 3
I0321 Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) 2
I0327 Insulator, Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE 1
R1113 Split-Bolt, Crossarm 1
T010+ Deadend, Preform 1
T030* Clamp, Straight Line Deadend 3
X0201 Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly 1
X0301 Crossarm, 10' Tangent Fiberglass 1
Z063+ Connector, Wedge 6
Z063* Connector, Wedge 2