12F311 - 3Ø Double Deadend
Revision 10
Jan 10, 2024
- Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
- Two primary down guys are required for line angles greater than 30°. Use one primary guy for line angles less than 30°.
- Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
- Crossarm to be set to split the angle in the line. Guys should be set in-line with the crossarm if possible.
- Maximum Line Angle: 60 degrees
Compatible Unit | Description | Quantity |
---|---|---|
A0102 | Anchor, 12" Single Helix | 1 |
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 30 |
G0111 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) | 1 |
G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 2 |
I0103 | Insulator, #2 Single Point Secondary Rack | 2 |
I0387 | Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 2 |
I0393 | Insulator, Dbl Stl Pole Top Pin w/ Polymer Vise-Top Insulator (For Pole Top Deadending Only) | 1 |
I0321 | Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) | 4 |
I0329 | Insulator, Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE | 1 |
R1115 | Split-Bolt, Pole Top | 2 |
T010+ | Deadend, Preform | 2 |
T030* | Clamp, Straight Line Deadend | 6 |
X0201 | Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly | 1 |
Z063* | Connector, Wedge | 2 |
Z063+ | Connector, Wedge | 6 |