12F611 - 3Ø Sectionalizer or Recloser Bank Type "GH", "4H" or "L"

Revision 3
Dec 5, 2011

 

Notes:

  1. This assembly is intended for use with 1Ø reclosers and sectionalizers.
  2. See wiring diagram, page 3 of 4.
  3. See Detail A, page 3 of 4, for disconnect spacing. Field drill and treat holes for switch installation.
  4. Install 90° terminal, Item S, on the load side of the disconnect switches feeding the sectionalizers or reclosers.

 

 

Material List

Compatible Unit Description Quantity
C0113 Wire, 336.4 kcmil AAC 19-str 60'
D0502 Switch, 600A 15kV Disconnect Xarm Mount 6
I0103 Insulator, Spool w/ Rack #2 1
I0307 Insulator, Pin #1177 4
I0315 Insulator, DE #1204 1
N0101 Rod, Ground 5/8” x 6' 1
R0303 Bracket, Cluster Mount 1
T030* Clamp, Straight Line 6
T0704 Terminal, Comp 90° 336.4 kcmil AAC 3
T0711 Terminal, Comp Captive Bolt 336.4 kcmil AAC 12
T0737 Terminal, Comp 336.4 kcmil AAC to 4/0 Cu Pin 6
T0924 Bar, Extension Terminal Single Tap 6
T0925 Bar, Extension Terminal Double Tap 3
T0953 Stainless Steel Bolt Assembly 6
X0414 Crossarm, Wood 4-Pin 10' 1
Z06* Connector, Wedge 9
Z06+ Connector, Squeezon Al 4
Z0701 Connector, Squeezon Cu (#150) #6-#2 to #6-#2 1