12F308 - 3Ø Deadend w/ Buck

Revision 12
Jul 10, 2018

 

Notes:

  1. Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
  2. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  3. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F365.

 

Material List

Compatible UnitDescriptionQuantity
A0102Anchor, 12" Single Helix2
C0550Tap Wire, Insul 4/0, Soft Drawn Copper45
G01113/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting)2
G01153/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment4
I0103Insulator, #2 Single Point Secondary Rack2
I0387Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount2
I0321Insulator, Sgl DE Insulator (Fittings: Clevis-Eye)4
I0327Insulator, Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE2
R1115Split-Bolt, Pole Top1
T010+Deadend, Preform2
T030*Clamp, Straight Line Deadend6
X0201Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly2
Z063+Connector, Wedge6
Z063*Connector, Wedge2