12U311 3Ø UG Terminal Pole with 200A SMD-20 Cutouts (1-0 Al)

Revision 4
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Note:

  1. System Planning & Protection will determine the need for the SMU-20 fuses based on coordination and loading calculations. See Assembly 12U309 &12U310 for typical fused underground assemblies
  2. Hang (3) spare fuses with (3) fuse-unit end fittings on eye nut and shackle.
  3. The concentric neutral from each cable shall be individually connected to the system neutral with an H-Type aluminum compression connector (see Compatible Unit Z0601 - Z0620).
 
Compatible Unit Description Qty
E0306 Cutout, With Spare Fuse-Unit End Fitting 3
E3---0 Fuses, SMU-20 6
F0213 Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 3
N0110 Ground Plate Installation on Wood Pole 1
R0102 Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) 3
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 3
R0630 Bolt, Machine 5/8" x 12" 1
R0734 Washer, Galv Double Coil Spring Lock 5/8" 1
R0744 Washer, 3" Sq with 13/16" Hole, Galv Steel 2
R1091 Shackle, Anchor Long 1
R1107 Nut, Eye 5/8" Bolt 1
T1013 Cable Term, 1/0 Al Jacketed & Unjacketed 3
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4
Z0704 Connector, C-Crimp Cu 2/0 - #2 3