12U311 3Ø UG Terminal Pole with 200A SMD-20 Cutouts (1-0 Al)
Revision 4
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- System Planning & Protection will determine the need for the SMU-20 fuses based on coordination and loading calculations. See Assembly 12U309 &12U310 for typical fused underground assemblies
- Hang (3) spare fuses with (3) fuse-unit end fittings on eye nut and shackle.
- The concentric neutral from each cable shall be individually connected to the system neutral with an H-Type aluminum compression connector (see Compatible Unit Z0601 - Z0620).
Compatible Unit | Description | Qty |
---|---|---|
E0306 | Cutout, With Spare Fuse-Unit End Fitting | 3 |
E3---0 | Fuses, SMU-20 | 6 |
F0213 | Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary | 1 |
K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 3 |
N0110 | Ground Plate Installation on Wood Pole | 1 |
R0102 | Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) | 3 |
R0206 | Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) | 3 |
R0630 | Bolt, Machine 5/8" x 12" | 1 |
R0734 | Washer, Galv Double Coil Spring Lock 5/8" | 1 |
R0744 | Washer, 3" Sq with 13/16" Hole, Galv Steel | 2 |
R1091 | Shackle, Anchor Long | 1 |
R1107 | Nut, Eye 5/8" Bolt | 1 |
T1013 | Cable Term, 1/0 Al Jacketed & Unjacketed | 3 |
X0301 | Crossarm, 10' Single Tangent Fiberglass | 1 |
Z010* | Clamp, Hotline | 3 |
Z060+ | Connector, H-Type Al Compression | 4 |
Z0704 | Connector, C-Crimp Cu 2/0 - #2 | 3 |