12U309 DE 3Ø UG Terminal Pole (2 or 1-0 Al)

Revision 11
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. This is the preferred installation for a 3Ø riser mounted on a deadend pole. If the conduit cannot be installed on the backside of the pole, refer to Assembly 12U310 for an alternate installation with the riser on the front of the pole.
  2. The concentric neutral from each cable shall be individually connected to the system neutral with an H-Type aluminum compression connector (see Compatible Unit Z0601 - Z0620).
 
Compatible Unit Description Qty
E0202 Cutout, With 100A Fuseholder 3
E1--- Fuses, "T" Link Primary Distribution 3
F0213 Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 3
N0110 Ground Plate Installation on Wood Pole 1
R0103 Bracket, Cutout Xarm Mount w/ 2, 3/8” x 8” CB 3
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 3
T101# Cable Termination Kit for Riser Poles 3
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4
Z0701 Connector, C-Crimp Cu #4 - #4 3