12U310 Alt DE 3Ø UG Terminal Pole (#2 or 1/0 Al)

Revision 11
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Assembly 12U309 is the preferred installation for a 3Ø riser mounted on a deadend pole. If the conduit must be installed on the front of the pole, then this Assembly may be used as an alternate.
  2. The concentric neutral from each cable shall be individually connected to the system neutral with an H-Type aluminum compression connector (see Compatible Unit Z0601 - Z0620).
 
Compatible Unit Description Qty
E0202 Cutout, With 100A Fuseholder 3
E1--- Fuses, "T" Link Primary Distribution 3
F0213 Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary 1
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 2
I0392 Insulator, 15kV Sgl Stl Pole Top Pin w/ Polymer Vise-Top Insulator (For Pole Top Deadending Only) 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 3
N0110 Ground Plate Installation on Wood Pole 1
R0103 Bracket, Cutout Xarm Mount w/ 2, 3/8” x 8” CB 3
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 3
T101# Cable Termination Kit for Riser Poles 3
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4
Z0701 Connector, C-Crimp Cu #4 - #4 3