12F605 - 3Ø Regulator Platform Mounting

Revision 15
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

 

 

Notes:

  1. Potential transformers and related material are optional and intended only for certain regulator bank installations. The engineer must specify the following compatible units separately:
    QtyCompatible UnitDescription
    1DB0310 3Ø P.T. Bank for Line Regulators
    3E0202 Cutout, 100A 15kV Polymer
    3R0102 Bracket, Cutout Crossarm Mounting
    1X0301DCrossarm, 10' Double Tangent Fiberglass
    3Z0102 Hot Line Clamp, No. 2 Al
  2. Regulators are not included with this assembly and must be specified separately. Refer to Section D for regulator compatible units.
  3. 12’ spacing is sufficient for regulators up to 250 kVA. For line regulators larger than 250 kVA increase platform to switch spacing to 14’.
  4. Bond and ground platform.
  5. See Compatible Unit F230, Control Cable Riser, when relocating existing control panels.
  6. Maximum allowable platform loading is 4,500 lbs. per regulator.
  7. Lightning arresters and control cables are supplied with the regulators.
  8. Minimum pole height is 50’.
  9. Secure regulators to platform by bolting regulator bases to platform supports and banding regulator tanks to the platform with 1/2” stainless steel banding and clips (items T & U).

Material List

Compatible Unit Description Quantity
C0208 Wire, #4 Cu Bare SD Sol 60'
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 120'
D0512 Switch, 600A 15.5kV Left-hand Source/Load/Bypass 3
DB0308 Bracket, Standoff with 12" T-Slot 1
I0105 Insulator, Spool w/ Rack #2 2
I0317 Insulator, 15kV Polymer Suspension 3
I0380 Insulator, 15kV Polymer Vertical Clamp Top 9
N0110 Plate, Cu Ground 288 in² 2
R0401 Equipment Mounting Platform, 14' Aluminum 1
R0802 Timbers, 6" x 8" x 16’-0" 1
R1113 Split-Bolt, Crossarm 4
T030* Clamp, Straight Line 6
T0704 OH Compression Terminals, 336.4 kcmil AAC 2-Hole (90°) 6
T0710 OH Compression Terminals, 336.4 kcmil AAC & ACSR Slotted Paddle 6
T0711 OH Compression Terminals, 336.4 kcmil AAC & ACSR Captive-Bolt Paddle 6
T0737 Stem Connector, 336.4 & 350 kcmil AAC Str 6
T0906 Dist Compression Terminal, 350 Str, 400 Compact Al & Cu 6
T0953 Stainless Steel Bolts, 1/2” x 1-3/4” 24
X0301 Crossarm, 10' Single Tangent Fiberglass 1
X0301D Crossarm, 10' Double Tangent Fiberglass 1
Z0603 Connector, Compression Al 2/0-3/0 to #6-1 to #6-1 3
Z060* Connector, Mini-Wedge 7
Z0701 Connector, C-Crimp #4 to #4 10