12F318 - 3Ø Buck Arm

Revision 8
Dec 28, 2017

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  3. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For framing conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F365.
  4. This assembly is intended for 3Ø bucks off distribution structures only. For transmission underbuild 3Ø bucks refer to Assembly Unit 12F318A.

 

 

Material List

Compatible Unit Description Quantity
A0102 Anchor, 12" Single Helix 1
G0111 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) 1
G0115 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment 2
I0103 Insulator, #2 Single Point Secondary Rack 1
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 1
I0321 Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) 2
I0327 Insulator, Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE 1
N0101 Single Ground Rod Installation 1
T010+ Deadend, Preform 1
T030* Clamp, Straight Line Deadend 3
X0201 Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly 1
Z060+ Connector, Compression 1