12F320 - 3Ø Underbuild Deadend w/ Buck
Revision 5
Jul 17, 2018
- Minimum arm to neutral separation is 7’-0”. Where possible, 8’-0” spacing is preferred.
- Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
- This assembly is intended to provide climbing space for deadend/buck installations on transmission structures. Refer to 12F308 for buck arm installations on distribution poles.
Compatible Unit | Description | Quantity |
---|---|---|
A0102 | Anchor, 12" Single Helix | 2 |
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 36 |
G0111 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) | 2 |
G0115 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment | 4 |
I0108 | Insulator, #2 Single Point Secondary Rack w/ 18" Bolt for Transmission Underbuild | 2 |
I0387 | Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 4 |
I0321 | Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) | 6 |
R1115 | Split-Bolt, Pole Top | 1 |
X0212 | Crossarm, 10' Deadend 4-Pos. Hvy. Duty | 2 |