12F320 - 3Ø Underbuild Deadend w/ Buck

Revision 5
Jul 17, 2018

Notes:

  1. Minimum arm to neutral separation is 7’-0”. Where possible, 8’-0” spacing is preferred.
  2. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  3. This assembly is intended to provide climbing space for deadend/buck installations on transmission structures. Refer to 12F308 for buck arm installations on distribution poles.

Material List

Compatible Unit Description Quantity
A0102 Anchor, 12" Single Helix 2
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 36
G0111 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) 2
G0115 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment 4
I0108 Insulator, #2 Single Point Secondary Rack w/ 18" Bolt for Transmission Underbuild 2
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 4
I0321 Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) 6
R1115 Split-Bolt, Pole Top 1
X0212 Crossarm, 10' Deadend 4-Pos. Hvy. Duty 2