12F327 - Double Circuit Flat Deadend

Revision 12
Jun 15, 2022

Notes:

  1. Minimum 8’-0”. Only to be installed on poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid conductor contact during fault conditions, install conductor spacers (Compatible Unit I0320A-B) on span lengths greater than 150 feet.
  4. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines

Material List

Compatible Unit Description Quantity
I0314 Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 6
N0110 Ground Plate Installation on Wood Pole 1
R1115 Split-Bolt, Pole Top 1
T030* Clamp, Straight Line Deadend
T0303 - 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC)

T0304 - 795 kcmil (336.4 - 1113 ACSR, 336.4 - 1200 AAC)
7
X02* Crossarm, 13' Deadend 6-Pos. Unitized Assembly
X0203 - 336.4 kcmil Medium Duty
X0213 - 795 kcmil Heavy Duty
1
Z0* Connector
Z0609 - 336.4 kcmil H-Type Al Compression
Z0735 - 795 kcmil Clamp 336.4-795 AAC to #6 Sol - 2/0 Str
1