12F207 7.2 12.47kV 2Ø Open Star Flat (60° - 90°) Angle

Revision 5
Oct 19, 2017

Notes:

  1. Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
  2. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
  3. 3Ø buck assemblies on joint poles will require a minimum 50' tall pole. 4. Do not specify preformed aluminum deadend C.U.’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends C.U. T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 2
G0115 Down Guy, Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment 2
I0103 Insulator, 600V #2 Single Point Secondary Rack 2
I0301 Insulator, 15kV Sgl Stl Pin (5/8" x 6-1/2" Shank) w/ Insulator, Xarm Mnt (5-3/4"H Max.) 2
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 4
R1115 Split Bolt Assembly, Pole Top 5/8" x 12" Machine Bolt 1
T010+ Deadend, Preformed 2
T030* Clamp, Straight Line 4
X0201 Crossarm, Fiberglass, 10' 2-Position Light Duty Unitized Deadend 2
Z063* Connector, Wedge 4
Z063+ Connector, Wedge 2