12U317 DE 3Ø Dbl Circuit UG Steel Terminal Pole (1100 kcmil Al)

Revision 6
Mar 13, 2020

Notes:

  1. Important! — Run a separate 4/0 Cu neutral bus conductor for each circuit.
  2. Individually connect each 1100 kcmil cable's concentric neutral (24 - #14 Cu, equivalent to 1/0 Cu) to the 4/0 Cu neutral bus. Extend each 4/0 Cu neutral bus down to the system neutral and connect it using the appropriate size wedge connector, i.e., Compatible Unit Z0637 4/0 Cu - 3/0 AAC; Z0642 4/0 Cu - 336.4 AAC; and Z0652 4/0 Cu - 795 AAC.
    See Compatible Unit Z0631 - Z0659 for wedge connectors for other neutral conductor sizes.
  3. This assembly is intended to meet the requirements of T&D Guideline 4-20-20.0 for working on energized distribution lines on steel poles. Variations of this framing may be acceptable as long as all energized conductors are mounted on non-conductive supports and a minimum of 15" clearance is maintained between any energized conductor and the steel pole.
  4. The fiberglass deadend crossarm must be ordered separately, depending on conductor size and tension:
    Compatible UnitDescriptionMax. Wire Size - Tension
    X020415' Medium Duty Fiberglass Crossarm336.4 kcmil AAC — 2,500 lb/Ø
    X021415' Heavy Duty Fiberglass Crossarm795 kcmil AAC — 4,500 lb/Ø
  5. Refer to Compatible Unit R0590 - R0598 for replacement hardware for lag screws.

 

 
Compatible Unit Description Qty
C0550 Tap Wire, Insul 4/0 Soft Drawn Copper 60
C0707 Wire, 4/0 Cu 19-Str SD 30
D0510 Switch, 3Ø Double-Circuit Gang-Operated Unitized 1
F0216 Riser, 6" PVC w/ 90° Fiberglass Bend - 3Ø 750 or 1000 kcmil Primary 2
I0306 Insulator, 15kV DE Porcelain Sgl Insulator 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 12
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 6
N0106 OBSOLETE - Ground Layout Distribution Switch Controls 1
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 6
T030+ Clamp, Straight Line 1
T030* Clamp, Straight Line 6
T0700 Compression Terminal, 336.4 kcmil AAC 2-Hole (Straight) 18
T0902 Compression Terminal, Flat Paddle 2/0 Str, 3/0 Compact Al & Cu 2
T0952 SS Bolt, 1/2” x 1-1/2” 4
T0954 SS Bolt, 1/2” x 2” 24
T1006 Cable Term, 1000 kcmil Al Jacketed 6
X02* Crossarm, Fiberglass 15' DE 1
X0303 Crossarm, 15' Single Fiberglass Tangent 6-Steel Pin Crossarm 1
Z0102 Clamp, Hotline Al (#2) #6-336.4 kcmil 6
Z065+ Connector, Wedge 2
Z0707 Connector, C-Crimp Cu 3/0-4/0 to #6-#2 6
Z0708 Connector, C-Crimp Cu 3/0-4/0 to 1/0-2/0 7