12U315 DE 3Ø Dbl Circuit UG Terminal Pole (1100kcm Al)
Revision 11
Mar 13, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Important! — Run a separate 4/0 Cu neutral bus conductor for each circuit.
- Individually connect each 1100 kcmil cable's concentric neutral (24 - #14 Cu, equivalent to 1/0 Cu) to the 4/0 Cu neutral bus. Extend the 4/0 Cu neutral bus down to the system neutral and connect it using the appropriate size wedge connector, i.e., Compatible Unit Z0637 4/0 Cu - 3/0 AAC; Compatible Unit Z0642 4/0 Cu - 336.4 AAC; and Compatible Unit Z0652 4/0 Cu - 795 AAC. See Compatible Unit page Z0631 - Z0659 for wedge connectors for other neutral conductor sizes.
Compatible Unit | Description | Qty |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 60 |
C0707 | Wire, 4/0 Cu 19-Str SD | 30 |
D0502 | Switch, 600A 15kV Disconnect Xarm Mount | 6 |
F0216 | Riser, 6" PVC w/ 90° Fiberglass Bend - 3Ø 750 or 1000 kcmil Primary | 2 |
K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 6 |
N0104 | Ground Rod with Ground Plate | 1 |
R0206 | Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) | 6 |
T0904A | Compression Terminal, 4/0 AWG 2-Hole (Straight) | 12 |
T0704A | Compression Terminal, 90° 2-Hole 4/0 AWG | 6 |
T0954 | SS Bolt, 1/2” x 2” | 24 |
T1006 | Cable Term, 1000 kcmil Al Jacketed | 6 |
X0302 | Crossarm, 13' Single Tangent Fiberglass Arms | 1 |
Z0102 | Clamp, Hotline Al (#2) #6-336.4 kcmil | 6 |
Z065+ | Connector, Wedge | 6 |
Z069+ | Connector, Wedge | 2 |
Z0707 | Connector, C-Crimp Cu 3/0-4/0 to #6-#2 | 1 |
Z0708 | Connector, C-Crimp Cu 3/0-4/0 to 1/0-2/0 | 6 |
Z0709 | Connector, C-Crimp Cu 3/0-4/0 to 3/0-4/0 | 6 |