12U314 3Ø UG Terminal Pole (1100kcm Al)
Revision 12
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Individually connect each 1100 kcmil cable's concentric neutral (24 - #14 Cu, equivalent to 1/0 Cu) to a 4/0 Cu neutral bus. Extend the 4/0 Cu neutral bus down to the system neutral and connect it using the appropriate size compression connector, i.e., Compatible Unit Z0607 4/0 Cu - 3/0 AAC and Compatible Unit Z0610 4/0 Cu - 336.4 AAC. See Compatible Unit page Z0601 - Z0620 for compression connectors of other neutral conductor sizes.
Compatible Unit | Description | Qty |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 30 |
C0707 | Wire, 4/0 Cu 19-Str SD | 15 |
D0502 | Switch, 600A 15kV Disconnect Xarm Mount | 3 |
F0216 | Riser, 6" PVC w/ 90° Fiberglass Bend - 3Ø 750 or 1000 kcmil Primary | 1 |
K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 3 |
N0110 | Ground Plate Installation on Wood Pole | 1 |
R0206 | Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) | 3 |
T0700 | Compression Terminal, 336.4 kcmil AAC 2-Hole (Straight) | 6 |
T0704 | Compression Terminal, 336.4 kcmil AAC 2-Hole (90°) | 3 |
T0954 | SS Bolt, 1/2” x 2” | 12 |
T1006 | Cable Term, 1000 kcmil Al Jacketed | 3 |
X0301 | Crossarm, 10' Single Tangent Fiberglass | 1 |
Z0102 | Clamp, Hotline Al (#2) #6-336.4 kcmil | 3 |
Z065+ | Connector, Wedge | 1 |
Z060+ | Connector, H-Type Al Compression | 1 |
Z0707 | Connector, C-Crimp Cu 3/0-4/0 to #6-#2 | 3 |
Z0708 | Connector, C-Crimp Cu 3/0-4/0 to 1/0-2/0 | 3 |
Z0709 | Connector, C-Crimp Cu 3/0-4/0 to 3/0-4/0 | 1 |