115P303 115kV Triangular Double Deadend Polymer (Uplift and Changes in Ruling Span)

Revision 14
Dec 4, 2018

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Pole setting depth: 10% of pole length plus 2 ft, per T&D Guideline 4-5-15.0.
  2. Quantity of T0955 is for 4-hole compression terminal connectors. Reduce this quantity to 4 for 2-hole compression terminal connections.
  3. Align top bracket vertically before drilling two 13/16" thru holes.
  4. Minimum clearance required between jumper and crossarm brace, pole or guy is 36".

Material List

Compatible Unit Description Quantity
A0102 12" Single Helix 2
G0304 Guy, 80' Pole, 1:1 Lead No Attachment Hardware (Med Loads) 4
I0701 Insulator, Polymer Suspension 115kV 6
I0703 Insulator, Vertical Post 115kV Polymer w/ o Bracket 1
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 1 Cu Yd
R100* Clamp, Line Post 1
R107* Clevis, Long Socket 6
R1301 2 Back-to-Back (3/4" x 18" Machine Bolts) 1
R1309 2 Back-to-Back (3/4" x 18" Machine Bolts) 1
R1401 Bracket, Pole Top 1
T060* Deadend, Comp Sgl Tongue 6
T070* Terminal, Comp 6
T0955 Terminal Lug Bolt 24
X0204 Xarm, Deadend 6-Pos. Unitized Assembly 1