115P303 115kV Triangular Double Deadend Polymer (Uplift and Changes in Ruling Span)
Revision 14
Dec 4, 2018
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Pole setting depth: 10% of pole length plus 2 ft, per T&D Guideline 4-5-15.0.
- Quantity of T0955 is for 4-hole compression terminal connectors. Reduce this quantity to 4 for 2-hole compression terminal connections.
- Align top bracket vertically before drilling two 13/16" thru holes.
- Minimum clearance required between jumper and crossarm brace, pole or guy is 36".
Compatible Unit | Description | Quantity |
---|---|---|
A0102 | 12" Single Helix | 2 |
G0304 | Guy, 80' Pole, 1:1 Lead No Attachment Hardware (Med Loads) | 4 |
I0701 | Insulator, Polymer Suspension 115kV | 6 |
I0703 | Insulator, Vertical Post 115kV Polymer w/ o Bracket | 1 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
R100* | Clamp, Line Post | 1 |
R107* | Clevis, Long Socket | 6 |
R1301 | 2 Back-to-Back (3/4" x 18" Machine Bolts) | 1 |
R1309 | 2 Back-to-Back (3/4" x 18" Machine Bolts) | 1 |
R1401 | Bracket, Pole Top | 1 |
T060* | Deadend, Comp Sgl Tongue | 6 |
T070* | Terminal, Comp | 6 |
T0955 | Terminal Lug Bolt | 24 |
X0204 | Xarm, Deadend 6-Pos. Unitized Assembly | 1 |