12F703 - 3Ø 600A 15kV Disconnect Switch Mounting w/ 3-100A Loadbreak Cutouts (Obsolete)

This Assembly is obsolete. Please see 12F706

Revision 15
Aug 27, 2020

Notes:

  1. Framing shown here requires approximately 8’-9” of pole space from brace lags to neutral. If insufficient pole space is available, framing X0412 should be used, as it requires only 7’-5” of vertical pole space.
  2. The individual tags used to make up a complete switch number must be specified by MID number. Refer to Compatible Unit W0201 for a complete list of switch number tag MID numbers. Specify enough tags to make up two switch numbers, one for each side of the pole.
  3. Insulated tap wire is suitable up to 336 AAC. Larger conductors will require bare jumpers.

 

Material List

Compatible UnitDescriptionQuantity
C05*Misc Insulated Tap Wire30'
D0502Switch, 600A 15kV Disconnect Xarm Mount3
E0202Cutout, 100A 15 kV Polymer3
I0103Insulator, Spool w/ Rack #21
I0322Insulator, 15kV Polymer Suspension4
I0329Insulator, 15kV Polymer Suspension1
R0102Bracket, Cutout Crossarm Mount3
T030*Clamp, Straight Line6
T0714Terminal, Comp Captive Bolt 4/0 kcmil AAC/CU6
T0924Bar, Extension Terminal Single Tap6
W0201Holder, Plastic 15kV OH Switch Number 21" x 4"2
X0301DCrossarm, 10' Double Tangent Fiberglass 1
Z010*Clamp, Hotline6
Z064*Connector, Mini-Wedge6