12F387 - 795 AAC 13' Double Circuit Deadend (Obsolete - See 12F327)

Revision 4
Aug 12, 2022

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid conductor contact during fault conditions, install conductor spacers (Compatible Unit I0320A-B) on span lengths greater than 150 feet.
  4. This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F327.
  5. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.

Material List

Compatible Unit Description Quantity
I0314 Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 6
N0110 Ground Plate Installation on Wood Pole 1
R1115 Split-Bolt, Pole Top 1
T0304 Clamp, Straight Line Deadend 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC) 7
X0213 Crossarm, 13' Deadend 6-Po. Hvy. Duty 1
Z0735 Connector, Clamp 336.4-795 AAC to #6 Sol - 2/0 Str 1