12F211 7.2 12.47kV 2Ø Open Star Flat Double Deadend (45° - 60°)
Revision 5
Nov 2, 2017
- Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
- Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
- Crossarm to be set to split the angle in the line. Guys should be set in-line with the crossarm if possible.
Compatible Unit | Description | Quantity |
---|---|---|
A0101 | Anchor, 8" Single Helix | 1 |
G0113 | Down Guy, Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 1 |
I0103 | Insulator, 600V #2 Single Point Secondary Rack | 1 |
I0321 | Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) | 2 |
I0387 | Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin FG Crossarm Mount | 4 |
R1115 | Split Bolt Assembly, Pole Top 5/8" x 12" Machine Bolt | 1 |
T030* | Clamp, Straight Line | 4 |
X0201 | Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly | 1 |
Z063* | Connector, Wedge | 4 |