12F211 7.2 12.47kV 2Ø Open Star Flat Double Deadend (45° - 60°)

Revision 5
Nov 2, 2017

Notes:

  1. Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
  2. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
  3. Crossarm to be set to split the angle in the line. Guys should be set in-line with the crossarm if possible.

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 1
G0113 Down Guy, Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 1
I0103 Insulator, 600V #2 Single Point Secondary Rack 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 2
I0387 Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin FG Crossarm Mount 4
R1115 Split Bolt Assembly, Pole Top 5/8" x 12" Machine Bolt 1
T030* Clamp, Straight Line 4
X0201 Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly 1
Z063* Connector, Wedge 4