12V115 7.2kV End-of-Arm Tap (From Existing 3Ø Line)

Revision 9
Oct 19, 2017

Notes:

  1. Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
  2. “T” link fuses must be ordered separately. Refer to Compatible Units E1001-E1200.
  3. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
  4. Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 1
E0202 Cutouts, 100A 15kV Open Type 1
G0113 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 1
I0308 Dbl Insulator - One-Way End-of-Arm DE 1
R0102 Bracket, Cutout 1
T010+ Deadend, Preformed 1
T030* Clamp, Straight Line 1
Z010* Clamp, Hotline 1
Z06* Connector, Wedge 1
Z060+ Connector, H-Type Al Compression 1