12V115 7.2kV End-of-Arm Tap (From Existing 3Ø Line)
Revision 9
Oct 19, 2017
- Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
- “T” link fuses must be ordered separately. Refer to Compatible Units E1001-E1200.
- Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
- Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).
Compatible Unit | Description | Quantity |
---|---|---|
A0101 | Anchor, 8" Single Helix | 1 |
E0202 | Cutouts, 100A 15kV Open Type | 1 |
G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 1 |
I0308 | Dbl Insulator - One-Way End-of-Arm DE | 1 |
R0102 | Bracket, Cutout | 1 |
T010+ | Deadend, Preformed | 1 |
T030* | Clamp, Straight Line | 1 |
Z010* | Clamp, Hotline | 1 |
Z06* | Connector, Wedge | 1 |
Z060+ | Connector, H-Type Al Compression | 1 |