12V113 7.2kV Vertical Tangent w Lateral
Revision 7
Dec 28, 2017
- Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
- Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).
Compatible Unit | Description | Quantity |
---|---|---|
A0101 | Anchor, 8" Single Helix | 1 |
G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 1 |
I0102 | Insulator, #1 Secondary Rack | 1 |
I0390 | Sgl Pole Top Pin w/ Polymer Vise-Top Insulator | 1 |
I0327 | Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE | 1 |
T010+ | Deadend, Preformed | 1 |
T030* | Clamp, Straight Line | 1 |
Z010* | Clamp, Hotline | 1 |
Z060+ | Connector, H-Type Al Compression | 2 |
Z06* | Connector, Wedge | 1 |