12V113 7.2kV Vertical Tangent w Lateral

Revision 7
Dec 28, 2017

Notes:

  1. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
  2. Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 1
G0113 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 1
I0102 Insulator, #1 Secondary Rack 1
I0390 Sgl Pole Top Pin w/ Polymer Vise-Top Insulator 1
I0327 Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE 1
T010+ Deadend, Preformed 1
T030* Clamp, Straight Line 1
Z010* Clamp, Hotline 1
Z060+ Connector, H-Type Al Compression 2
Z06* Connector, Wedge 1