12U308 3Ø UG Terminal Pole (2 or 1-0 Al)
Revision 17
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
Note:
- The concentric neutral from each cable shall be individually connected to the system neutral with an H-Type aluminum compression connector (see Compatible Unit Z0601 - Z0620).
| Compatible Unit | Description | Qty |
|---|---|---|
| E0202 | Cutout, With 100A Fuseholder | 3 |
| E1--- | Fuses, "T" Link Primary Distribution | 3 |
| F0213 | Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary | 1 |
| K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 3 |
| N0110 | Ground Plate Installation on Wood Pole | 1 |
| R0102 | Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) | 3 |
| R0206 | Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) | 3 |
| T101# | Cable Termination Kit for Riser Poles | 3 |
| X0301 | Crossarm, 10' Single Tangent Fiberglass | 1 |
| Z010* | Clamp, Hotline | 3 |
| Z060+ | Connector, H-Type Al Compression | 4 |
| Z0701 | Connector, C-Crimp Cu #4 - #4 | 3 |