115F307 115kV Flat Top Double Deadend

Revision 7
Mar 30, 2012

Notes:

  1. If excessive down angle causes insulator to interfere with crossarm, suspension insulator may be relocated to lower crossarm mounting bolt.
  2. Maximum vertical weight (W) not to exceed 1,500 lbs. per phase.
  3. Maximum transverse load (P) on crossarm not to exceed 1,500 lbs.
  4. Crossarm deflection will be 3” with a horizontal tension (T) of 3,800 lbs. per phase. Maximum horizontal tension (T) not to exceed 6,000 lbs. per phase.

 

 

Material List

Compatible Unit Description Quantity
I0701 Insulator, Polymer Suspension 115kV 6
I0703 Insulator, Vertical Post 115kV Polymer w/ o Bracket 3
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 1 Cu Yd
R100* Clamp, Line Post 3
R107* Clevis, Long Socket 6
R1401 Bracket, Pole Top 115kV 1
R1402 Plate, Mounting Double Arm 2
T060* Deadend, Comp Sgl Tongue 6
T070* Terminal, Comp 6
T0955 Bolt, SS 1/2" x 2-1/2" 24
X0805 Crossarm, Fiberglass 18' 1