115F307 115kV Flat Top Double Deadend
Revision 7
Mar 30, 2012
- If excessive down angle causes insulator to interfere with crossarm, suspension insulator may be relocated to lower crossarm mounting bolt.
- Maximum vertical weight (W) not to exceed 1,500 lbs. per phase.
- Maximum transverse load (P) on crossarm not to exceed 1,500 lbs.
- Crossarm deflection will be 3” with a horizontal tension (T) of 3,800 lbs. per phase. Maximum horizontal tension (T) not to exceed 6,000 lbs. per phase.
Compatible Unit | Description | Quantity |
---|---|---|
I0701 | Insulator, Polymer Suspension 115kV | 6 |
I0703 | Insulator, Vertical Post 115kV Polymer w/ o Bracket | 3 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
R100* | Clamp, Line Post | 3 |
R107* | Clevis, Long Socket | 6 |
R1401 | Bracket, Pole Top 115kV | 1 |
R1402 | Plate, Mounting Double Arm | 2 |
T060* | Deadend, Comp Sgl Tongue | 6 |
T070* | Terminal, Comp | 6 |
T0955 | Bolt, SS 1/2" x 2-1/2" | 24 |
X0805 | Crossarm, Fiberglass 18' | 1 |