12F368 - 3Ø 795 AAC Deadend w/ Buck
Revision 6
Jul 17, 2018
Notes:
- 50’ minimum pole height.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to Compatible Unit Sections A and G.
- This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of no more than 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F308.
Compatible Unit | Description | Quantity |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 45 |
I0313 | Insulator, Sgl Insulator w/ 18" Eye Bolt - One-Way Pole Mount DE | 2 |
I0321 | Insulator, Sgl DE Insulator (Fittings: Clevis-Eye) | 4 |
I0327 | Insulator, Sgl DE Insulator w/ 14” Eye Bolt - One-Way Pole Mount DE | 2 |
I0387 | Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 2 |
R1115 | Split-Bolt, Pole Top | 1 |
T0303 | Clamp, Straight Line 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC) | 2 |
T0304 | Clamp, Straight Line 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC) | 6 |
X0212 | Crossarm, 10' Deadend 4-Pos. Hvy. Duty | 2 |
Z0640 | Connector, Wedge 336.4 AAC/ACSR to 336.4 AAC/ACSR | 4 |
Z0650 | Connector, Wedge 795 AAC/ACSR to 795 AAC/ACSR | 6 |