12F366 - 3Ø 795 AAC Flat Double Deadend

Revision 4
Jul 17, 2018

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
  4. This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of no more than 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F311.

Material List

Compatible UnitDescriptionQuantity
C0550Tap Wire, Insul 4/0 Soft Drawn Copper40
I0315Insulator, Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE1
I0321Insulator, Sgl DE Insulator (Fittings: Clevis-Eye)4
I0329Insulator, Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE1
I0387Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount2
I0392Insulator, Sgl Stl Pole Top Pin w/ Polymer Vise-Top Insulator (For Pole Top Deadending Only)1
T0303Clamp, Straight Line 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC)2
T0304Clamp, Straight Line 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC)6
X0212Crossarm, 10' Deadend 4-Pos. Hvy. Duty1
Z0640Connector, Wedge 336.4 AAC/ACSR to 336.4 AAC/ACSR2
Z0650Connector, Wedge 795 AAC/ACSR to 795 AAC/ACSR6