12F333 Obsolete - 336.4 AAC 4-over-2 Double Circuit Deadend w/ Buck
Revision 5
Jul 19, 2018
- 55' minimum pole height.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
- This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F393.
- New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.
Compatible Unit | Description | Quantity |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 72 |
I0387 | Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 6 |
I0313 | Insulator, 15kV DE Porcelain Sgl Insulator w/ 18" Eye Bolt - One-Way Pole Mount DE | 2 |
I0321 | Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) | 12 |
T0303 | Clamp, Straight Line Deadend 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC) | 14 |
X0201 | Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly | 2 |
X0212 | Crossarm, 10' Deadend 4-Pos. Hvy. Duty | 2 |
Z0640 | Connector, Wedge 336.4 - 336.4 kcmil AAC/ACSR | 14 |