12F332 Obsolete - 336.4 AAC 4-over-2 Double Circuit Double Deadend
Revision 3
Jul 18, 2018
- Minimum 50' pole height.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
- Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
- This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F392.
- New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.
Compatible Unit | Description | Quantity |
---|---|---|
C0550 | Tap Wire, Insul 4/0 Soft Drawn Copper | 60 |
I0301 | Insulator, 15kV Sgl Stl Pin (5/8" x 6-1/2" Shank) w/ Insulator, Xarm Mnt (5-3/4"H Max.) | 6 |
I0315 | Insulator, 15kV DE Porcelain Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE | 1 |
I0321 | Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) | 12 |
T0303 | Clamp, Straight Line Deadend 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC) | 14 |
X0201 | Crossarm, 10' Deadend 3-Pos. Lt. Duty Unitized Assembly | 1 |
X0212 | Crossarm, 10' Deadend 4-Pos. Hvy. Duty | 1 |
Z0640 | Connector, Wedge 336.4 - 336.4 kcmil AAC/ACSR | 14 |