12F328 - Double Circuit Flat Double Deadend

Revision 5
Jun 15, 2022

Notes:

  1. Minimum 8’-0”. Only to be installed on poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid conductor contact during fault conditions, install conductor spacers (Compatible Unit I0320A-B) on span lengths greater than 150 feet.
  4. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For framing conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F388.
  5. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines

 

Material List

Compatible Unit Description Quantity
I0387 Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 6
I0315 Insulator, 15kV DE Porcelain Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE 1
I0323 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye)
12
T030* Clamp, Straight Line Deadend
T0303 - 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC)
T0304 - 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC)
14
X0203 Crossarm, 13' Deadend 6-Pos. Unitized Assembly 1
Z06* Connector, Wedge
Z0640 - 336.4 - 336.4 kcmil AAC/ACSR
Z0650 - 795 to 795 kcmil AAC/ACSR
14