12V107 7.2kV Vertical 60° - 90° Corner

Revision 4
Oct 19, 2017

Notes:

  1. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
  2. Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 2
G0113 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 2
I0101 Insulator, #1 Single Point Secondary Rack 2
I0327 Insulator, 15kV Polymer Suspension 2
T010+ Deadend, Preformed 2
T030* Clamp, Straight Line 2