12V107 7.2kV Vertical 60° - 90° Corner
Revision 4
Oct 19, 2017
- Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.
- Do not specify preformed aluminum deadend Compatible Unit’s (T010+) if the neutral is #6 or #4 solid Cu. Instead, specify flexible bail automatic deadends Compatible Unit T0508 (for #6 solid Cu) or T0509 (for #4 solid Cu).
Compatible Unit | Description | Quantity |
---|---|---|
A0101 | Anchor, 8" Single Helix | 2 |
G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 2 |
I0101 | Insulator, #1 Single Point Secondary Rack | 2 |
I0327 | Insulator, 15kV Polymer Suspension | 2 |
T010+ | Deadend, Preformed | 2 |
T030* | Clamp, Straight Line | 2 |