12U321 Typical 7.2 12.47kV 3Ø Primary Metering Underground Terminal Pole (2 or 1-2 Al 15kV Cables)
Revision 16
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Important! Contact Metering Department for cost estimates on material and labor for installing primary metering equipment.
- See T&D Guideline 4-17-20.0 for schematic drawing of CT/PT and arrester connections.
- The concentric neutral from each cable shall be individually connected to the system neutral with a mini-wedge.
Compatible Unit | Description | Qty |
---|---|---|
E0202 | Cutout, With 100A Fuseholder | 3 |
F0213 | Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary | 1 |
K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 3 |
N0104 | Ground Rod with Ground Plate | 1 |
R0102 | Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) | 3 |
R0206 | Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) | 3 |
T101# | Cable Termination Kit for Riser Poles | 3 |
X0301 | Crossarm, 10' Single Tangent Fiberglass | 1 |
Z010* | Clamp, Hotline | 3 |
Z060+ | Connector, H-Type Al Compression | 4 |
Z0701 | Connector, C-Crimp Cu #4 - #4 | 4. |