12U321 Typical 7.2 12.47kV 3Ø Primary Metering Underground Terminal Pole (2 or 1-2 Al 15kV Cables)

Revision 16
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Important! Contact Metering Department for cost estimates on material and labor for installing primary metering equipment.
  2. The concentric neutral from each cable shall be individually connected to the system neutral with a mini-wedge.
 
Compatible Unit Description Qty
E0202 Cutout, With 100A Fuseholder 3
F0213 Riser, 4" PVC w/ 90° Fiberglass Bend - 3Ø #2 & 1/0 Primary 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 3
N0104 Ground Rod with Ground Plate 1
R0102 Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) 3
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 3
T101# Cable Termination Kit for Riser Poles 3
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4
Z0701 Connector, C-Crimp Cu #4 - #4 4.