12U211 2Ø UG Terminal Pole (2 or 1-0 Al)

Revision 16
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Material List

Compatible Unit Description Quantity
E0202 Cutouts, 100A 15kV Open Type 2
F0212 Riser, 4" PVC w/ 90° Fiberglass Bend - 2Ø #2 & 1/0 Primary 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 2
N0110 Ground Plate Installation on Wood Pole 1
R0102 Bracket, Cutout Crossarm Mount w/ 3/8" x 6" Carriage Bolts (For Standard 7', 10', 11' & 13' Crossarms) 2
R0206 Bracket, Cable Term Crossarm-Mount (#1 Pothead Bracket) 2
T101# Cable Termination Kit for Riser Poles 2
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 2
Z060+ Connector, H-Type Al Compression 1