12U111 1Ø UG Terminal Pole (2 or 1-0 Al)

Revision 18
Mar 13, 2020

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. The engineer shall specify the proper cutout bracket. Refer to Compatible Unit R0101 - R0103
  3. The engineer shall specify the proper 15kV Underground cable termination. Specify Compatible Unit T1012 for #2 cable and T1013 for 1/0 cable.
  4. C.U. N0110 (Ground Plate Installation) is for new pole installations only. When attaching risers to existing poles, use C.U. N0101 (Single Ground Rod Installation).

Material List

Compatible Unit Description Quantity
E0202 Cutouts, 100A 15kV Open Type 1
F0211 Riser, 2" PVC w/ 90° Steel Bend - 1Ø #2 & 1/0 Primary 1
K0201 Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV 1
N0110 Ground Plate Installation on Wood Pole 1
R0205 Bracket, Cable Term Pole-Mount Standoff Support, 24" Fiberglass 1
T101# Cable Termination Kit for Riser Poles 1
Z010* Clamp, Hotline 1
Z060+ Connector, H-Type Al Compression 1
Z0701 Connector, C-Crimp Cu #4 to #4 1