12U111 1Ø UG Terminal Pole (2 or 1-0 Al)
Revision 18
Mar 13, 2020
- Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
- The engineer shall specify the proper cutout bracket. Refer to Compatible Unit R0101 - R0103
- The engineer shall specify the proper 15kV Underground cable termination. Specify Compatible Unit T1012 for #2 cable and T1013 for 1/0 cable.
- C.U. N0110 (Ground Plate Installation) is for new pole installations only. When attaching risers to existing poles, use C.U. N0101 (Single Ground Rod Installation).
Compatible Unit | Description | Quantity |
---|---|---|
E0202 | Cutouts, 100A 15kV Open Type | 1 |
F0211 | Riser, 2" PVC w/ 90° Steel Bend - 1Ø #2 & 1/0 Primary | 1 |
K0201 | Arrester, Overhead, MOV, 10kV Duty-Cycle / 8.4kV MCOV | 1 |
N0110 | Ground Plate Installation on Wood Pole | 1 |
R0205 | Bracket, Cable Term Pole-Mount Standoff Support, 24" Fiberglass | 1 |
T101# | Cable Termination Kit for Riser Poles | 1 |
Z010* | Clamp, Hotline | 1 |
Z060+ | Connector, H-Type Al Compression | 1 |
Z0701 | Connector, C-Crimp Cu #4 to #4 | 1 |