12F720 - 3Ø 600A 15kV Gang-Operated Distribution Automation Switch

Revision 1
Nov 16, 2021

Notes:

  1. Preferred spacing between switch arm and neutral is 5’-0”. Minimum allowable spacing is 4’-0”.
  2. Important — connect control transformer to source side! Control transformer is internally fused and does not require a cutout.
  3. 90 degree terminal bar extensions available T0924-6

Material List

Compatible Unit Description Quantity
BA10B Xfmr, Control Power 1kVA 120V 1
C0113 Wire, 336.4 kcmil AAC 19-Str 36'
D0530 Switch, OH 600A 15kV 3Ø SCADA Compatible 1
F0230 3" PVC - Control Cable 1
K0201 Arrester, Surge 10kV 6
T030* Clamp, Straight Line 6
T0700 Terminal, Comp Straight 336.4 kcmil AAC 6
T0955 Stainless Steel Bolt, 1/2” x 2-1/2” 12
W0201 Holder, Plastic 15kV OH Switch Number 21" x 4" 2
Z0102 Clamp, Hotline Al (#2) #6-336.4 kcmil 7
Z0603 Connector, Compression Al 2/0-3/0 to #6-#1 1
Z063* Connector, Wedge 6
Z0701 Connector, C-Crimp Cu #4-#4 10
Z0704 Connector, C-Crimp Cu 1/0 Sol - 2/0 Str to #8 Sol - #2 Str 2