12F304 - 3Ø 10' Double Arm Line Angle

Revision 5
Aug 27, 2020

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
  3. Crossarm to be set to split the angle in the line. Guys should be set in-line with the crossarm if possible.

 

Material List

Compatible UnitDescriptionQuantity
A0101Anchor, 8" Single Helix1
G01113/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting)1
G01133/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads)1
I0103Insulator, #2 Single Point Secondary Rack1
I0387Insulator, Sgl Polymer Vise-Top Insulator4
I0391Insulator, Dbl Pole Top Pin w/ Polymer Vise-Top Insulator1
X0301DCrossarm, 10' Double Tangent Fiberglass 1