12F302 - 3Ø 7' Double Arm Line Angle
Revision 5
Jul 18, 2023
- This standard should be used only when horizontal clearances will not permit the use of a 10’ crossarm. Refer to 12F304 for the District’s preferred 3Ø large angle tangent framing assembly.
- Down guys and anchors specified are based on 336.4 kcmil AAC primary and 3/0 AAC neutral with a maximum guy attachment height/guy lead ratio of 2:1.
Compatible Unit | Description | Quantity |
---|---|---|
A0101 | Anchor, 8" Single Helix | 1 |
G0111 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads,1-Bolt/2-Lag Mounting) | 1 |
G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 1 |
I0103 | Insulator, #2 Single Point Secondary Rack | 1 |
I0387 | Insulator, Sgl Polymer Vise-Top Insulator | 4 |
I0391 | Insulator, Dbl Pole Top Pin w/ Polymer Vise-Top Insulator | 1 |
X0300D | Crossarm, 7' Double Fiberglass | 1 |