12F408 - 336.4 AAC 3-over-3 Double Circuit Deadend Underbuild (Obsolete - See 12F403)
Revision 2
Aug 12, 2022
- 50’ minimum pole height without communication attachments. 60’ minimum pole height with communication attachments.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
- To avoid accidental contact with jumpers, primary down guys must be equipped with 144" fiberglass guy strain insulators (MID 939267). Refer to T&D Guideline 4-6-1.5 for more information on use and placement of guy strain insulators.
- The upper circuit on 3-over-3 double circuit structures is an express feeder. Connect all transformers, risers and 1Ø and 2Ø taps to the lower circuit
- This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F418.
- New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.
Compatible Unit | Description | Quantity |
---|---|---|
I0314 | Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE | 1 |
I0321 | Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) | 6 |
N0110 | Ground Plate Installation on Wood Pole | 1 |
T0303 | Clamp, Straight Line Deadend 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC) | 7 |
X0212 | Crossarm, 10' Deadend 4-Pos. Hvy. Duty | 2 |
Z0609 | Connector, H-Type Al Compression | 1 |