12F386 - Double Circuit Flat Deadend w/ Buck (795 AAC Only)

Revision 4
Jan 12, 2017

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid conductor contact during fault conditions, install conductor spacers (Compatible Unit I0320A-B) on span lengths greater than 150 feet.
  4. This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F326.
  5. New overhead double circuit construction is allowed in rural areas only.

Material List

Compatible Unit Description Quantity
I0314 Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE 2
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 12
I0389A Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 10" Pin HD Fiberglass Crossarm Mount 6
R1091 Shackle, Anchor Long 1
R1115 Split-Bolt, Pole Top 1
T0304 Clamp, Straight Line Deadend 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC) 14
X0213 Crossarm, 13' Deadend 6-Po. Hvy. Duty 2
Z0650 Connector, Wedge 795 to 795 kcmil AAC/ACSR 14