12F386 - Double Circuit Flat Deadend w/ Buck (795 AAC Only)

Revision 4
Jan 12, 2017

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid conductor contact during fault conditions, install conductor spacers (Compatible Unit I0320A-B) on span lengths greater than 150 feet.
  4. This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F326.
  5. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.

Material List

Compatible Unit Description Quantity
I0314 Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE 2
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 12
I0389A Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 10" Pin HD Fiberglass Crossarm Mount 6
R1091 Shackle, Anchor Long 1
R1115 Split-Bolt, Pole Top 1
T0304 Clamp, Straight Line Deadend 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC) 14
X0213 Crossarm, 13' Deadend 6-Po. Hvy. Duty 2
Z0650 Connector, Wedge 795 to 795 kcmil AAC/ACSR 14