12F130 7.2kV 1Ø Flat Deadend Arm

Revision 3
Jun 5, 2017

Notes:

  1. Neutrals deadended on primary crossarms must be installed on 15kV porcelain suspension insulators or otherwise identified. Refer to T&D Guideline 4-16-3.3.
  2. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1.

Material List

Compatible Unit Description Quantity
A0101 Anchor, 8" Single Helix 1
G0115 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) - No Attachment 1
I0306 Insulator, DE #1204 1
I0321 Insulator, 15kV Polymer Suspension 1
R1115 Split-bolt Assembly, Pole Top 1
T030* Clamp, Straight Line 2
X0201 Crossarm, 10’ 2-Pos Light Duty DE 1