1U708 1Ø Secondary Riser (4in) & Large Underground Service Handhole or Vault with 5-Position Terminal Bars
Revision 8
Jun 27, 2016
- Secondary risers must be installed no lower than the system neutral to provide proper clearance from communication attachments.
- The maximum number of cables in handhole V0101 shall not exceed limits given in V0101 - V0104.
- Refer to T&D Guideline 4-17-15.0 for acceptable combinations of cable and conduit sizes.
Compatible Unit | Description | Quantity |
---|---|---|
F0107 | Riser, 4" PVC w/ 90° PVC Bend - Secondary | 1 |
F0304 | Conduit, 4" NEMA TC-2 Sch 40 w/ 1-Belled End | As Req. |
F0385 | Conduit, Corrugated Flexible PVC 4" | 4 |
F0714 | Coupling, Conduit PVC 4" Sch 40 Deep Socket | 1 |
F0904 | End, Bell PVC 4" Sch 40 | 1 |
T1522 | Terminal, Submrs Set Screw Res 5-Pos #10-350 kcmil | 3 |
As Req | Large Handhole or Vault | 1 |