1U708 1Ø Secondary Riser (4in) & Large Underground Service Handhole or Vault with 5-Position Terminal Bars

Revision 8
Jun 27, 2016

Notes:

  1. Secondary risers must be installed no lower than the system neutral to provide proper clearance from communication attachments.
  2. The maximum number of cables in handhole V0101 shall not exceed limits given in V0101 - V0104.
  3. Refer to T&D Guideline 4-17-15.0 for acceptable combinations of cable and conduit sizes.

Material List

Compatible Unit Description Quantity
F0107 Riser, 4" PVC w/ 90° PVC Bend - Secondary 1
F0304 Conduit, 4" NEMA TC-2 Sch 40 w/ 1-Belled End As Req.
F0385 Conduit, Corrugated Flexible PVC 4" 4
F0714 Coupling, Conduit PVC 4" Sch 40 Deep Socket 1
F0904 End, Bell PVC 4" Sch 40 1
T1522 Terminal, Submrs Set Screw Res 5-Pos #10-350 kcmil 3
As Req Large Handhole or Vault 1