115F301 115kV Flat Top (Tangent)

Revision 5
Nov 9, 2023

Notes:

  1. Maximum vertical weight (W) not to exceed 1,500 lbs. per phase.
  2. Maximum horizontal pull (P) on insulator not to exceed 1,500 lbs.

Material List

Compatible Unit Description Quantity
I0703 Insulator, Vertical Post 115kV Polymer w/ o Bracket 3
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 1 Cu Yd
R100* Clamp, Line Post 3
R1401 Bracket, Pole Top 115kV 1
R1402 Plate, Mounting Double Arm 2
X0805 Crossarm, Fiberglass 18' 1