12V613 - Low-Power Radio Installation on Service/Guy Poles
Revision 4
Feb 7, 2019
- The foreign utility will provide the metering equipment, aluminum bracket, power cord, fasteners, and connectors.
- Radio units require 120/240 volt service. If a service is not available, then triplex service wire must be run from an adjacent service location. Refer to Compatible Units C0300 and C0301.
- The radio unit must be bonded. If no ground is present, install a #4 bare SD solid copper bond wire (MID 848476) from the concentrator unit ground point to the system neutral.
- Contact the Joint Use department a minimum of 2 weeks before relocation of a unit in order to coordinate with the proper foreign utility representative.
- Assembly 12V613 may only be used on service and guy stub poles. See Assembly 12V613A for installation on a primary distribution pole.
Compatible Unit | Description | Quantity |
---|---|---|
I0109 | Insulator, Spool w/ Rack #1 | |
N0101 | Rod, Ground 5/8" x 8' | |
PF0154 | Pole Top Extension, Fiberglass 54" | |
R0626 | Bolt, Machine 5/8" x 8" | |
R0630 | Bolt, Machine 5/8" x 12" | |
R0734 | Washer, Galv Double Coil Spring Lock 5/8” | 4 |
R0744 | Washer, Galv Sq 3" Curved 13/16" Hole | 4 |
Z060+ | Connector, H-Type Al Compression | 1 |
Z0701 | Connector, C-Crimp Cu #4 to #4 | 1 |