12V613 - Low-Power Radio Installation on Service/Guy Poles

Revision 4
Feb 7, 2019

Notes:

  1. The foreign utility will provide the metering equipment, aluminum bracket, power cord, fasteners, and connectors.
  2. Radio units require 120/240 volt service. If a service is not available, then triplex service wire must be run from an adjacent service location. Refer to Compatible Units C0300 and C0301.
  3. The radio unit must be bonded. If no ground is present, install a #4 bare SD solid copper bond wire (MID 848476) from the concentrator unit ground point to the system neutral.
  4. Contact the Joint Use department a minimum of 2 weeks before relocation of a unit in order to coordinate with the proper foreign utility representative.
  5. Assembly 12V613 may only be used on service and guy stub poles. See Assembly 12V613A for installation on a primary distribution pole.

Material List

Compatible Unit Description Quantity
I0109 Insulator, Spool w/ Rack #1  
N0101 Rod, Ground 5/8" x 8'  
PF0154 Pole Top Extension, Fiberglass 54"  
R0626 Bolt, Machine 5/8" x 8"  
R0630 Bolt, Machine 5/8" x 12"  
R0734 Washer, Galv Double Coil Spring Lock 5/8” 4
R0744 Washer, Galv Sq 3" Curved 13/16" Hole 4
Z060+ Connector, H-Type Al Compression 1
Z0701 Connector, C-Crimp Cu #4 to #4 1