12V612 - Landis & Gyr Wireless Receiver Station
Revision 5
Dec 28, 2017
- This standard addresses installation of Landis & Gyr (formerly known as Cellnet) wireless metering facilities in District supply space. All work in the supply space will be performed by District crews or pre-qualified overhead line contractors. Landis & Gyr will provide the communications enclosure, MCC unit, antennas, coax, 90° 2” sweeps, aluminum bracket, power cord and connectors.
- Landis & Gyr metering facilities require 120/240 volt service. If a transformer is not available on the Landis & Gyr installation pole, then triplex service wire must be run from an adjacent service location. Refer to Compatible Units C0300 and C0301.
- The Landis & Gyr communications enclosure must be bonded. If no ground is present, install a #4 bare SD solid copper bond wire (MID 848476) from the communications enclosure to the system neutral.
- Contact the Joint Use department a minimum of 3 days before relocation of unit in order to coordinate with the proper Landis & Gyr representative.
Compatible Unit | Description | Quantity |
---|---|---|
C0301 | Wire, #6 Al TPX 600V OH | 3' |
F0302 | Conduit, PVC 2” Sch 40 Gray | 40' |
F0902 | End, Bell PVC 2" Sch 40 | 4 |
R0203 | Bracket, Standoff 15” | 3 |
R0205 | Bracket, Fiberglass Support | 1 |
R0703 | Bolt, DA 5/8” x 22” | 2 |
R0734 | Washer, Galv Double Coil Spring Lock 5/8” | 4 |
R0744 | Washer, Galv Sq 3" Curved 13/16" Hole | 4 |
Z060+ | Connector, H-Type Al Compression | 1 |
Z0701 | Connector, C-Crimp Cu #4 to #4 | 1 |