12F339 - 3Ø 7' Braceless Alley Arm Tangent
Revision 4
Feb 17, 2026
Notes:
- Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
- Down guy(s) may be omitted on tangent poles with no large unbalanced power or communication attachments if the following steps are taken to avoid excessive pole deflection.
- Increase pole setting depth a minimum of 10% of length + 4 feet.
- Install expanding pole keys per Compatible Unit PF0100.
- Backfill with crushed rock tamped in 6" lifts.
- Rake the pole away from the line as follows:
Max Wire Size: #2 ACSR, Rake: 2"
Max Wire Size: 336.4 kcmil, Rake: 4"
Down guy(s) or self-supporting poles are required for 795 kcmil alley arm framing.
- Refer to T&D Guideline 4-23-1.0 for allowable construction angles.
| Compatible Unit | Description | Quantity |
|---|---|---|
| A0102 | Anchor, 12" Single Helix | 1 |
| G0113 | 3/8" Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) | 1 |
| I0103 | Insulator, #2 Single Point Secondary Rack | 1 |
| I0390 | Insulator, Sgl Pole Top Pin w/ Polymer Vise-Top Insulator | 1 |
| I0388 | Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 8" Pin Fiberglass Crossarm Mount | 2 |
| X0551 | Crossarm, 7' Fiberglass Alley Arm | 1 |