12F407 - 336.4 AAC 3-over-3 Double Circuit Double Deadend Underbuild (Obsolete - 12F402)

Revision 3
Aug 12, 2022

Notes:

  1. 50’ minimum pole height without communication attachments. 60’ minimum pole height with communication attachments.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid accidental contact with jumpers, primary down guys must be equipped with 144" fiberglass guy strain insulators (MID 939267). Refer to T&D Guideline 4-6-1.5 for more information on use and placement of guy strain insulators.
  4. The upper circuit on 3-over-3 double circuit structures is an express feeder. Connect all transformers, risers and 1Ø and 2Ø taps to the lower circuit
  5. Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
  6. This assembly is intended for primary conductors with a maximum working tension of 2,500 lb/Ø or less. For deadending conductors with a maximum working tension between 2,500 lb/Ø and 4,000 lb/Ø refer to Assembly Unit 12F417.
  7. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.

Material List

Compatible Unit Description Quantity
I0387 Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 6
I0315 Insulator, 15kV DE Porcelain Dbl DE Assembly w/ 20” D.A. Bolt - Two-Way Pole Mount DE 1
I0321 Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) 12
T0303 Clamp, Straight Line Deadend 336.4 kcmil (3/0 - 477 kcmil ACSR, 4/0 - 556 kcmil AAC) 14
X0212 Crossarm, 10' Deadend 4-Pos. Hvy. Duty 2
Z0640 Connector, Wedge 336.4 - 336.4 kcmil AAC/ACSR 14